Model No. |
UPS-POW-1500APR |
|
AC Input Capacity on Battery |
1500VA |
|
AC Input Frequency |
50 or 60 Hz +/- 10% (auto sensing) |
|
AC Input Voltage |
(+/-) 25% at line input |
|
AC Output Frequency |
50 or 60 Hz +/- 0.5% |
|
AC Output Transfer |
2/4 milliseconds, including detection time |
|
AC Output Voltage |
Simulated sine wave at 100V or 110V/115V/120V or 220V/230V/240V +/-5% |
|
AC Output Voltage Regulation |
AVR automatically increase output voltage 15% above input voltage if -9% to -25% of nominal. AVR decrease output voltage 13% below input voltage if +9% to +25% of nominal |
|
Alarm Battery Backup |
Slow beeping sound (about 0.47 Hz) |
|
Alarm Battery Low |
Rapid beeping sound (about 1.82Hz) |
|
Alarm Overload |
Continue beeping sound |
|
Battery Protection |
Automatic self-test & discharge protection, replace battery indicator |
|
Battery Run Time |
70 - 80 minutes |
|
Battery Type |
Sealed, maintenance-free lead acid |
|
Battery Typical |
8 hours (to 90% of full capacity) |
|
Environment Ambient |
3,500 meters max. elevation, 0-95% humidity non-condensing, 0-40 deg c |
|
Environment Audible |
<40dBA (1 meter from surface) |
|
Environment Storage Condition |
15,000 meters max. elevation |
|
Indicator |
LED |
|
Interface Option |
RS-232 |
|
Protection 10 BaseT |
Network (UTP, RJ-45) compatible jacks |
|
Protection EMI/RFI |
10dB at 0.15 MHz, 50 dB at 30 MHz |
|
Protection Overload |
UPS automatic shutdown if overload exceeds 110% nominal at 60 sec and 130% at 3 sec |
|
Protection Short Protection |
UPS output cut off immediately or input fuse protection |
|
Protection Spike |
320 Joules, 2ms |
|
Protection Unit |
Fuse for overload & short circuit protection |
|
Dimensions |
19" x 14" x 3.3" (2U RM) |
|
Weight |
35.2 Lbs / 16 Kg |
UPC: 790932215848